Busbar Systems
Paktronics Test panel was constructed to an IP54 rating to comply with Water Authority (WIMES) specifications, but this had a detrimental effect on the Temperature Rise Tests due to the lack of available ventilation. This was overcome through a change of metalwork design within the busbar sections and some added internal ventilation systems.
This is particularly useful for Sewage Treatment sites where copper busbars can be affected by H2S gases causing them to discolour. Paktronic can replace the affected busbars with new tinned busbars that will not be affected by the gases, while still utilising the existing panel structure. Replacing stolen/vandalised busbar systems can also be offered as part of our on-site services.